[email protected]  |  +86 027 85808426 WhatsAppGet a Quote

VLF (0.1 Hz) Withstand Testing for Medium-Voltage Cables

Test voltage table, real tester specifications and factory field notes — numbers taken directly from our technical documentation and nameplates, not rewritten from textbooks.

Why this page is different

Written by the manufacturer, not a copywriter

Yoanpower is the export brand of Wuhan Defu Electric (est. 1983), and our 0.1 Hz VLF high voltage generators are built to comply with the Chinese power industry standard DL/T 849.4-2004 (General technical requirements for ultra-low frequency high voltage generators). Everything on this page is copied from our own product manuals, factory test setup photos and nameplates. Where we don't have verified data, we say so instead of guessing.

Block 1 · Reference tableSource: factory technical data sheet (0.1 Hz test voltage setting table)

VLF test voltage for XLPE cables — acceptance & maintenance

Set the test voltage as Umax = 3 × U0, where U0 is the rated phase voltage of the cable (formula from our manual). All voltage values below are peak values, applied at 0.1 Hz, true sine wave. Acceptance (hand-over) test duration is 60 min; maintenance (preventive) test duration is 15 min — both copied verbatim from our manual. Voltage classes not listed in our factory table (11 / 15 / 24 kV) are struck through.

System
voltage
Cable U0/U
(kV)
Acceptance test
(hand-over)
Maintenance test
(preventive)
FrequencyValue
type
Standard basis
6 kV3.6/6 or 6/63U0 = 11 / 18 kV peak
60 min
3U0 = 11 / 18 kV peak
15 min
0.1 HzPeakFactory data sheet, citing DL/T 849.4-2004 and the Chinese industry standard “Test method of 0.1 Hz voltage withstand test for XLPE insulated power cables up to 35 kV”. Setting rule: Umax = 3U0.
10 kV6/10 or 8.7/103U0 = 18 / 26 kV peak
60 min
3U0 = 18 / 26 kV peak
15 min
0.1 HzPeak
20 kV12/203U0 = 36 kV peak
60 min
3U0 = 36 kV peak
15 min
0.1 HzPeak
35 kV21/35 or 26/353U0 = 63 / 78 kV peak
60 min
3U0 = 63 / 78 kV peak
15 min
0.1 HzPeak
11 kVNot in our factory table. By the manual's 3U0 rule with the IEC U0 = 6.35 kV, that works out to ≈19 kV peak — derived, not from the table; confirm with us before a hand-over test.
15 kVNot in our factory table. By 3U0 with U0 = 8.7 kV: ≈26 kV peak — derived; confirm with us.
24 kVNot covered by our documentation — uncertain. Send us your cable's U0 and we will confirm the setting.

Frequency: 0.1 Hz is the standard test frequency. Our generators also output 0.05 / 0.02 / 0.01 Hz for high-capacitance test objects (see load table below).
Value type: peak (crest) values — our instruments display peak voltage and current, per the manual.
Standards basis: our factory documents reference DL/T 849.4-2004 (general technical requirements for 0.1 Hz VLF generators) and the Chinese industry standard “Test method of ultra-low frequency (0.1 Hz) voltage withstand test for XLPE insulated power cables up to 35 kV”. Levels from IEC 60502-2 / IEEE 400.2 are not listed in these documents — if your project is specified to IEEE 400.2, contact us and our engineers will convert the settings for you.

Block 2 · Hardware specificationsSource: product manual (touch-screen version) & factory photos

YAVLF series 0.1 Hz VLF hipot tester — the actual numbers

ItemSpecification (copied from manual / nameplate)
Rated output voltage30 / 40 / 50 / 60 / 80 / 90 kV peak (models 30/1.1 – 90/1.1)
Output frequency0.1 Hz, 0.05 Hz, 0.02 Hz, 0.01 Hz (selectable)
Load capacity0.1 Hz: ≤ 0.5 µF  ·  0.05 Hz: ≤ 1.1 µF  ·  0.02 Hz: ≤ 2.2 µF  ·  0.01 Hz: ≤ 5.5 µF
Output waveformSine wave (electronic type; high/low voltage closed-loop negative feedback, no capacitive voltage rise effect)
Measurement accuracy3%; positive/negative peak error ≤ 3%; voltage waveform distortion ≤ 5%
ProtectionOver-voltage + over-current protection on both HV and LV sides; protection action time ≤ 10 ms; automatic discharge of the test object after the test
Power supplyAC 220 V ± 5%, 50 ± 5 Hz; fuse 10 A (30/40 kV models), 15 A (50–90 kV models); if powered by a portable generator: > 3 kW, 50 Hz, 220 V ± 5%
WeightController: 4 kg (7" capacitive touch screen version). Booster: 20 kg (30 kV set), 45 kg (60 kV set); 90 kV set uses 40 kg + 20 kg booster sections plus compensation capacitor (see factory photo above)
Data & reportingBuilt-in thermal printer, USB port, automatic storage of up to 64 test records, automatic print-out of test reports, Chinese/English interface switching
Operating conditionsIndoor / outdoor; temperature −10 °C to +40 °C; humidity ≤ 85% RH
Minimum loadTest object capacitance below 0.05 µF affects the output waveform — a 0.05 µF compensation capacitor (supplied by us) is connected in parallel in that case
Partial discharge / tanδ optionsNot mentioned in the current datasheets — uncertain. Ask us for the latest configuration options.

Test current can be estimated before the test with the manual's formula I = 2πfCU (C = cable capacitance to earth in µF, U = test voltage in kV).
Note: an earlier English datasheet lists a 6 kg controller for this series; the current Chinese manual for the touch-screen version states 4 kg — figures above follow the current manual.

Block 3 · A real site recordSite photos from the job · numeric record pending test report

Field record: VLF withstand test, 35 kV PV plant collection circuits

We performed cable fault detection and VLF withstand testing of the 35 kV collection circuits for a grid-connected PV plant (see our Projects page). The photos above were taken on the job. We will publish the complete numeric record — cable model and cross-section, length, measured capacitance, applied test voltage and duration, result and total on-site time — only after we have verified every figure against the original test report. We will not fill this table with rounded or reconstructed numbers.

ItemValue
Industry / locationGrid-connected PV plant, 35 kV collection circuit
Cable type & cross-sectionUncertain — pending original test report
Cable lengthUncertain — pending original test report
Measured capacitanceUncertain — pending original test report
Applied voltage & durationUncertain — pending original test report
Result (pass / breakdown / retest)Uncertain — pending original test report
Total on-site timeUncertain — pending original test report
Block 4 · Things that go wrong on siteFrom our manuals & service experience
Burned and exploded XLPE cable end beside a 0.1 Hz VLF test set — one procedural mistake is enough to destroy a healthy cable
One procedural mistake is enough to destroy a healthy cable — precision, patience, procedure, every time

VLF Withstand Testing: 5 Critical Field Lessons

VLF testing seems simple, but poor execution leads to inaccurate data—or worse, cable breakdown. These five hard-earned lessons must not be ignored:

  1. Always discharge before testing. Residual charge in the insulation can stack with test voltage and cause breakdown. After megger testing, discharge for at least 5 minutes.
  2. Keep terminations clean. Moisture or contamination causes flashover at the ends, masking the true condition of the cable body. Clean thoroughly and apply shielding if needed.
  3. Never exceed test voltage. VLF test voltage is typically around 1.7× operating voltage. Overvoltage can damage healthy cables. For maintenance (preventive) testing the level may be lower than for acceptance testing.
  4. Allow sufficient duration. The standard requires 60 minutes of sustained voltage. Shortening the test time fails to reveal hidden defects—rendering the test useless.
  5. Discharge again after testing. Charge dissipates much slower under VLF than power frequency. Wait at least 10 minutes before handling connections.

Strict adherence to procedures is non-negotiable.

Three more we check before energising

Short cable, no output. A test object below 0.05 µF capacitance will not output a proper waveform — every one of our sets ships with a 0.05 µF compensation capacitor for exactly this case; connect it in parallel and the waveform comes back. (Documented in our manual, and the red capacitor in the photos above is it.)

Long cable eats the capacity budget. At 0.1 Hz the load limit is only 0.5 µF. Don't order a bigger booster — drop the frequency: 0.05 Hz takes 1.1 µF, 0.02 Hz takes 2.2 µF, 0.01 Hz takes 5.5 µF. Run I = 2πfCU with your cable length first, then pick the frequency.

Unstable site generator. If the output looks wrong on site, check the power source first: our manual requires a portable generator of more than 3 kW, stable 50 Hz, 220 V ± 5%. Undersized gensets are the most common cause of unexplained trips.

Testing a different voltage class or cable length? Send us U0, cross-section and length — our engineers will size the set and confirm the settings.

Ask an engineer — reply within 24 h

Need a VLF tester sized for your cables?

Tell us your cable voltage class, length and test standard — we will propose the right model and quote within 24 hours.

Send Inquiry