[email protected]  |  +86 027 85808426 WhatsAppGet a Quote

Relay Protection Tester & Primary Injection Test Set — Hard Specs, Test Checklist & Field Notes

Three of our relay test sets side by side — the 6-phase YA1200C, the 3-phase YA802C and the 3-phase YA702C — with the numbers copied from our own manuals, the test items we run on every job, one real substation record and the mistakes we keep making. Written by the manufacturer, not a copywriter.

Why this page is different

Written by the manufacturer, not a copywriter

Yoanpower is the export brand of Wuhan Defu Electric (est. 1983). Our relay protection testers are built to comply with DL/T 624-2010 (technical specifications for microcomputer-based relay protection test equipment) and the relay-protection verification rules of DL/T 995-2016 / GB/T 7261-2016. Every number in Block 1 is copied from our own product manuals and nameplates — no web-sourced guesses, no "typical" figures.

Block 1 · Hard specificationsSource: YA1200C / YA802C / YA702C factory manuals (DF1200C / DF802C / DF702C)

YA1200C (6-phase) · YA802C (3-phase) · YA702C (3-phase) — the actual numbers

The three main relay test sets we push. YA1200C is our 6-current / 6-voltage unit for three-phase transformer differential and busbar schemes; YA802C is the 4-voltage / 3-current workhorse with an industrial PC + Windows for fast on-site work; YA702C is the same 4U3I hardware with a single-chip controller and knob operation for the budget job. YA-xxx is the export designation — the same units ship domestically as DF1200C / DF802C / DF702C. Every number below is copied from our own factory manuals, not a web listing. The only difference between YA802C and YA702C is the controller; their electrical outputs are identical.

AttributeYA1200C — 6-phaseYA802C — 3-phaseYA702C — 3-phase
Output phases / channels6× current + 6× voltage, freely combinable (6U6I / 4U3I / 12-phase modes)4× voltage + 3× current (standard 4U3I), industrial PC + Windows4× voltage + 3× current (standard 4U3I), single-chip / knob control
Per-phase current outputAC 0–30 A / phase (6-phase mode) · 0–60 A / phase (3-phase mode)AC 0–40 A / phaseAC 0–40 A / phase
Parallel (total) current6-phase parallel: 0–180 A (allowed 10 s)3-phase parallel: 0–120 A (allowed 10 s)3-phase parallel: 0–120 A (allowed 10 s)
Voltage outputAC phase 0–120 V / line 0–240 V · DC 0–±160 V / phase (±320 V line)AC phase 0–120 V / line 0–240 V · DC 0–±160 V / phase (±320 V line)AC phase 0–120 V / line 0–240 V · DC 0–±160 V / phase (±320 V line)
Accuracy class0.2 class (AC & DC)0.2 class (AC) · 0.5 class (DC)0.2 class (AC) · 0.5 class (DC)
Output powerCurrent 450 VA / phase · 1000 VA (6-parallel) · Voltage 80 VA (phase) / 100 VA (line)Current 450 VA / phase · 900 VA (3-parallel) · Voltage 80 VA (phase) / 100 VA (line)Current 450 VA / phase · 900 VA (3-parallel) · Voltage 80 VA (phase) / 100 VA (line)
Channels — switch & timing8 binary inputs / 4 binary outputs · time 0.1 ms–9999 s (<0.1 ms resolution)8 binary inputs / 4 binary outputs · time 0.1 ms–9999 s (0.1 ms resolution)8 binary inputs / 4 binary outputs · time 0.1 ms–9999 s (0.1 ms resolution)
Controller / interfaceIndustrial PC + Windows, mouse-wheel control, PC connectableIndustrial PC + Windows, mouse-wheel control, PC connectableSingle-chip, knob control, non-Windows, no PC connection
Frequency / harmonicsBase frequency 0–1000 Hz · harmonics 0–20thBase frequency 0–1000 Hz · harmonics 0–20thBase frequency 0–1000 Hz (PC-linked) · 0–300 Hz (standalone) · 0–20th harmonics
Aux. DC supplyIndependent 110 V / 220 V adjustable DC, 1.5 AIndependent 110 V / 220 V adjustable DC, 1.5 AIndependent 110 V / 220 V adjustable DC, 1.5 A

YA802C vs YA702C: these two share the same 4U3I electrical platform (0–40 A / phase, 0–120 A parallel, 0.2-class AC). The difference is the controller — YA802C runs an industrial PC with Windows and mouse-wheel control for fast menu work; YA702C uses a single-chip board with knob operation and no PC link, at a lower price. Pick the controller that fits the operator and the budget.
Domestic = export mapping: YA1200C = DF1200C, YA802C = DF802C, YA702C = DF702C. The YA-xxx name is what we put on export units; the DF-xxx name is the domestic catalogue number.
Primary vs secondary injection: the YA1200C / YA802C / YA702C are secondary-injection relay test sets (they inject into the protection terminals / CT & VT secondary). For primary injection commissioning of circuit breakers, CT ratios and overall trip chains we supply separate high-current primary injection test sets — tell us the primary current you need and we will point you to the right unit.

Protection Relay Tester Series model comparison: YA1200C 6-phase with 6 current and 6 voltage outputs, YA-802C 3-phase with Windows system and mouse-wheel control, YA-702C 3-phase with knob control and non-Windows system
Our Protection Relay Tester Series — YA1200C (6 current + 6 voltage outputs, Windows system, PC connectable, mouse-wheel control), YA-802C (3 current + 4 voltage outputs, Windows/IPC, mouse-wheel, PC connectable) and YA-702C (3 current + 4 voltage outputs, knob control, non-Windows, no PC connection). YA-xxx is the export designation; the same units ship domestically as DF1200C / DF802C / DF702C.
Block 2 · Mandatory test checklistSource: YA1200C / YA802C / YA702C factory manuals — relay-type vs test-module tables

The test items we run before a protection is cleared

This list is lifted directly from the relay-type / test-module matrix in our own manuals (the same table our engineers follow on site). It covers both conventional relays and microprocessor-based protection. Tick them off in order; the three-phase units run most items through the “AC test” module, and the six-phase DF1200C is what you need for three-phase transformer differential.

  • Binary input / output check — verify dry-contact and 0–250 V potential contacts, trip / close contacts.
  • Measurement accuracy — voltage, current, phase angle, frequency against a reference meter.
  • Over-current protection — definite-time and inverse-time (I–t characteristic) elements.
  • Over- / under-voltage protection — pickup and drop-off of voltage elements.
  • Distance protection — multi-stage setting, impedance characteristic, zero-sequence compensation.
  • Zero-sequence / negative-sequence — 3I0 / 3U0 elements, sequence-component output.
  • Power-direction protection — sensitive angle and action boundary (90° / 0° wiring).
  • Differential protection — ratio restraint, harmonic restraint, DC magnetising (3-phase needs 6-current DF1200C).
  • Auto-reclosing — check-sync / check-no-voltage logic.
  • Automatic synchronising device — speed / voltage matching, slip setting.
  • End-to-end / overall trip test — line protection integrated test, fault-type sweep.
  • Frequency & under-frequency load-shedding — df/dt blocking, slip setting.
  • Conventional relay calibration — time, intermediate, signal, auxiliary relays.
  • Time characteristic — operate / return time, return coefficient at ≥1.2× setting.

Standards we test against: DL/T 995-2016 (relay protection device inspection regulations), GB/T 7261-2016 (basic test methods for relays and protection equipment) and IEC 60255 series. For a project specified to a particular utility's acceptance criteria, send us the setting sheet and we will map every item above to it.

Block 3 · A real site recordDevice models from our manual appendix · numeric record pending original test report

Field record: 110 kV substation, line & feeder protection commissioning

The protection models below (Nari RCS-900 series) are exactly the devices listed in our own manual's relay-application appendix, so the combination is realistic. As with our VLF page, we will publish the full numeric record — measured pickup / drop-off values, applied currents and voltages, total on-site time and the result — only after we have verified every figure against the original test report. We will not fill this table with rounded or reconstructed numbers.

ItemRecord
Substation voltage level110 kV (line & feeder protection commissioning)
Protection make & modelNari RCS-941A / RCS-943 (110 kV line protection, per our manual appendix) — typical on this class of substation
Test set usedYA702C / YA802C (3-phase) for line / feeder; YA1200C (6-phase) brought in for any transformer differential on site
Tests performedMulti-stage over-current, distance & zero-sequence setting, auto-reclosing (check-sync / check-no-voltage), overall trip test, binary I/O check, time characteristic
Time spentUncertain — pending original test report
Problems encounteredUncertain — pending original test report
ResultUncertain — pending original test report

Want your own record here? Send us the substation voltage class, the protection make / model and the setting sheet — our engineers will run the Block 2 checklist and return a verified, item-by-item report you can publish.

Avoid 3 common relay testing mistakes for more accurate and reliable results — YA-802C protection relay tester
Block 4 · Things that go wrong on siteFrom our manuals & service experience

Three pitfalls we keep hitting

These are not textbook warnings — they are the mistakes our own manuals explicitly call out, and the ones our field engineers hit most often.

  1. Binary-input polarity is wired backwards. The common terminal of the binary input must be connected to the positive side of the contact power (+KM). If you reverse it, the tester simply cannot detect the contact — the protection looks like it never operated. Our manual states this in bold; check polarity before every timing test.
  2. Thin, long leads on a high-current output. When paralleling phases for 100 A+ (YA1200C up to 180 A, YA802C / YA702C up to 120 A), all parallel phases must be at the same phase angle, and you must use short, thick cable. Long or thin leads drop voltage, distort the waveform and ruin the accuracy — and the 10-second parallel window is not a margin, it is a limit.
  3. Timing measured the wrong way. Measuring operate time by creeping the current up manually gives wrong numbers. Output at least 1.2× the pick-up (or ≤0.8× for under-voltage) so the relay definitely operates, and for under-frequency / df/dt-blocking elements use the automatic ramp — manual stepping cannot hold the slip rate the relay expects.

One more, non-negotiable: never switch the tester off while it is outputting — the wrong value at shutdown can trip the protection you are testing.

Two more we check before energising

Line vs phase voltage on the setting sheet. Low-voltage and negative-sequence settings are often given as line voltage (UL) but the tester outputs phase voltage (Uph). Divide by √3 (≈1.732) before you set it, or the relay will never reach its pick-up. Our manual flags this exact conversion.

Multi-stage over-current tested one stage at a time. When checking stage I, exit stages II and III first, then ramp the current. If you leave the later stages armed, the operate time you read for stage I is wrong — the relay may have acted on a downstream element. Stage-by-stage is the only way to get a clean time reading.

Not sure which relay test set fits your substation — 6-phase or 3-phase? Send us the protection make / model and the voltage class; our engineers will size it and quote within 24 hours.

Ask an engineer — reply within 24 h

Need a relay protection tester sized for your protection?

Tell us the protection make / model, voltage class and which test items you must run — we will propose YA1200C, YA802C or YA702C and quote within 24 hours.

Send Inquiry