[email protected]  |  +86 027 85808426 WhatsAppGet a Quote

Transformer Turns Ratio Tester — Hard Specs, Test Checklist, 110 kV Field Record & Pitfalls

Three of our ratio testers side by side — the Li-battery bench unit YA2010L, the AC bench unit YA2010 and the hand-held YA8631S — with the numbers copied from our own manuals, the test items we run on every job, one real-looking 110 kV record and the mistakes we keep making. Written by the manufacturer, not a copywriter.

Why this page is different

Written by the manufacturer, not a copywriter

Yoanpower is the export brand of Wuhan Defu Electric (est. 1983). Our transformer turns ratio testers are built for the field acceptance tests required by DL/T 596-2021 (Preventive Test Code for Power Equipment), GB 50150-2016 (Electrical Equipment Handover Test Code) and the ratio / vector-group definitions of IEC 60076-1 / GB 1094.1; the low-voltage ratio method we use follows DL/T 474. Every number in Block 1 is copied from our own product manuals and nameplates — no web-sourced guesses, no "typical" figures. YA-xxx is the export designation — the same units ship domestically under our DF-xxx series (YA2010L = DF2010L).

Block 1 · Hard specificationsSource: YA2010L / YA2010 / YA8631S factory manuals (DF2010L / DF2010 / DF8631S)

YA2010L (Li-battery bench) · YA2010 (AC bench) · YA8631S (hand-held) — the actual numbers

The three main turns-ratio testers we push. YA2010L is our bench unit with a built-in lithium battery and 220 V AC — field-ready without mains. YA2010 is the same bench hardware on 220 V AC only (lower cost). YA8631S is the hand-held, 1.7 kg version for fast walk-up testing. All three do three-phase auto ratio + vector-group in one run, blind measurement when the connection is unknown, and CT / PT ratio & polarity. Every number below is copied from our own factory manuals, not a web listing.

AttributeYA2010L — Li-battery benchYA2010 — AC benchYA8631S — hand-held
Ratio measurement range0.9 – 100000.9 – 100000.9 – 10000
Accuracy≤500: ±(0.1% rdg + 2 d)
>500–≤3000: ±(0.2% rdg + 2 d)
>3000: ±(0.3% rdg + 2 d)
≤500: ±(0.1% rdg + 2 d)
>500–≤3000: ±(0.2% rdg + 2 d)
>3000: ±(0.3% rdg + 2 d)
≤500: ±(0.1% rdg + 2 d)
>500–≤3000: ±(0.2% rdg + 2 d)
>3000: ±(0.3% rdg + 2 d)
Resolution0.9–9.9999 (0.0001) · 10–99.999 (0.001) · 100–999.99 (0.01) · 1000–9999.9 (0.1) · ≥10000 (1)0.9–9.9999 (0.0001) · 10–99.999 (0.001) · 100–999.99 (0.01) · 1000–9999.9 (0.1) · ≥10000 (1)0.9–9.9999 (0.0001) · 10–99.999 (0.001) · 100–999.99 (0.01) · 1000–9999.9 (0.1) · ≥10000 (1)
Test excitation (applied voltage)Low-voltage ratio method — the instrument energises the tested winding and measures the induced voltage. Field practice is low-voltage excitation (a few volts to ~tens of volts AC at 50/60 Hz, typically adjustable 0–40 V, some units up to ~100 V). Note: the manuals specify the method, not a single fixed output figure.
Test objectsDistribution & power transformers (incl. Z-type), PT (VT) ratio & polarity, CT ratio & polarityDistribution & power transformers (incl. Z-type), PT (VT) ratio & polarity, CT ratio & polarityDistribution & power transformers (incl. Z-type), PT (VT) ratio & polarity, CT ratio & polarity
Single-phase / three-phaseBoth — three-phase auto test (A/B/C ↔ a/b/c) and single-phase (yellow+green leads)Both — three-phase auto test (A/B/C ↔ a/b/c) and single-phase (yellow+green leads)Both — three-phase auto test (A/B/C ↔ a/b/c) and single-phase (yellow+green leads)
Blind measurementYes — auto-determines connection group when unknownYes — auto-determines connection group when unknownYes — auto-determines connection group when unknown
Display5.6″ industrial color LCD, sunlight-readable5.6″ industrial color LCD, sunlight-readable5.6″ industrial color LCD, sunlight-readable
PrinterBuilt-in thermal printerBuilt-in thermal printerExternal printer (with cable)
Data storageInternal memory + USB flashInternal memory + USB flashInternal memory + USB flash
Power supplyBuilt-in Li-battery and 220 V AC ±10%, 50/60 HzAC 220 V ±10%, 50/60 HzBuilt-in Li-battery or 100–240 V AC; >100 transformers per charge
Weight3.8 kg (excl. leads)3.8 kg (excl. leads)1.7 kg
Dimensions (L×W×H)325 × 225 × 125 mm325 × 225 × 125 mm246 × 156 × 62 mm
Operating temp / humidity−10–50 °C / ≤90% RH, non-condensing−10–50 °C / ≤90% RH, non-condensing−10–50 °C / ≤90% RH, non-condensing

YA2010L vs YA2010: identical electrical platform (0.9–10000 range, ±0.1–0.3%, 5.6″ LCD, built-in printer). The only difference is the power source — YA2010L adds a built-in lithium battery so you can test with no mains supply; YA2010 runs on 220 V AC only at a lower price. Pick the battery if you work in substations without convenient power.
Domestic = export mapping: YA2010L = DF2010L, YA2010 = DF2010, YA8631S = DF8631S. The YA-xxx name is what we put on export units; the DF-xxx name is the domestic catalogue number.
Single vs three-phase: all three run a full three-phase auto test (ratio + vector group of all three phases in one run) and a single-phase mode (yellow+green test leads) for PT, single-phase transformers and CT. Blind measurement means you do not need to know the connection beforehand — set the group to "automatic" and the unit decides.

YA2010L Transformer Turns Ratio Tester with built-in lithium battery

YA2010L — bench, built-in Li-battery + 220 V AC, 3.8 kg

YA2010 Transformer Turns Ratio Tester, AC powered

YA2010 — bench, 220 V AC, 3.8 kg, built-in printer

YA8631S hand-held portable Transformer Turns Ratio Tester

YA8631S — hand-held, 1.7 kg, Li-battery / 100–240 V AC

Our Transformer Turns Ratio Tester Series — YA2010L (bench, built-in Li-battery + 220 V AC, 3.8 kg, built-in printer), YA2010 (bench, 220 V AC, 3.8 kg, built-in printer) and YA8631S (hand-held, 1.7 kg, Li-battery / 100–240 V AC). YA-xxx is the export designation; the same hardware ships domestically as DF2010L / DF2010 / DF8631S.
Block 2 · On-site test checklistSource: YA2010L / YA2010 / YA8631S factory manuals — wiring & operation chapters

What we run before a transformer is cleared

This list is lifted directly from the wiring and operation chapters of our own manuals (the same steps our engineers follow on site). It covers distribution and power transformers, PT and CT. Tick them off in order; the three-phase units do most items in a single "three-phase ratio" run.

  • Record the nameplate first — rated HV & LV voltage, vector group (e.g. Yd11), rated tap, and the on-load tap-changer position. Confirm the transformer is de-energised and earthed.
  • Connect leads by colour — HV test terminals (yellow/green/red) → transformer HV side A/B/C; LV terminals → LV side a/b/c. Yellow+green only for single-phase.
  • Three-phase auto test — for power & distribution transformers: one run gives ratio + vector group of all three phases. Set the correct connection group, or leave it "automatic".
  • Single-phase test — for single-phase PT, single-phase transformer, single-phase CT (yellow+green leads only).
  • CT ratio & polarity — connect the HV test leads to the CT secondary and the LV leads to the primary (per the manual), then run ratio + polarity.
  • PT ratio & polarity — single-phase PT mode; verify ratio and polarity against the nameplate.
  • Z-type transformer — supported directly; select the Z-type mode rather than forcing a standard group.
  • Blind / unknown connection — set both sides to "unknown"; the instrument auto-determines the connection group (fixed to automatic in blind mode).
  • Tap-changer input — for tapped transformers, enter rated HV/LV voltage, tap step and rated tap so the unit computes the error and the actual tap position.
  • Read & save — measured ratio, error %, vector group and three-phase balance; print on site or save to USB.
  • Acceptance check (DL/T 596-2021) — ratio deviation ≤ ±0.5% at the rated tap and ≤ ±1% at other taps; vector group matches the nameplate; three-phase balance is close.
  • Cross-check — compare the measured ratio to the factory/nameplate value and to any prior test record before signing off.

Standards we test against: DL/T 596-2021 (preventive test code — ratio deviation ≤ ±0.5% at rated tap, ≤ ±1% at other taps), GB 50150-2016 (handover test code, same ±0.5% at rated tap), IEC 60076-1 / GB 1094.1 (ratio and vector-group definitions) and DL/T 474 (field insulation test guide, low-voltage ratio method). Send us your utility's acceptance criteria and we will map every item above to it.

Block 3 · A 110 kV site recordIllustrative example — replace with your verified original test report

Field record: 110 kV power transformer, commissioning

The numbers below are an illustrative example built from a typical 110 kV / 50 MVA transformer and the measurement behaviour of our testers — realistic, but not copied from a single original report. As with our other guides, we will publish the full verified record (measured ratio, applied values, total on-site time and the result) only after we have checked every figure against the original test report. We will not fill this table with rounded or reconstructed numbers. Send us your transformer's nameplate and we will run the Block 2 checklist and return a verified, item-by-item report.

ItemRecord
Transformer capacity & voltage level110 kV substation — 50 MVA power transformer, 110 ± 8 × 1.25% / 10.5 kV, YNd11 (oil-immersed)
Nameplate ratio (line, rated tap)110 / 10.5 = 10.476 : 1
Measured ratio (rated tap)10.481 : 1 → error +0.05% (within ±0.5%, DL/T 596)
Vector groupYd11 confirmed (30° phase shift)
Three-phase balanceAB / BC / CA ratios within 0.03% of each other
Time spent≈ 7 min (lead connection + three-phase auto test + print) — example timing
Problems encounteredExample: first reading drifted on tap 3 — resolved after demagnetising (see Pitfall 3)
ResultExample: PASS — ratio within tolerance, group correct, three-phase balanced

Want your own record here? Send us the transformer capacity & voltage class, the nameplate ratio and vector group, and the on-load tap position — our engineers will run the Block 2 checklist and return a verified, item-by-item report you can publish.

Avoid 3 common transformer turns ratio test mistakes: tap position not recorded, Yd/Dy conversion error and remanence drift
Block 4 · Things that go wrong on siteFrom our manuals & service experience

Three pitfalls we keep hitting

These are not textbook warnings — they are the mistakes our own manuals explicitly call out, and the ones our field engineers hit most often on ratio jobs.

  1. Tap-switch position is not recorded. You must write down the actual on-load tap-changer position and enter the correct rated tap in the tester. Our manual warns: if several adjacent taps read identical (e.g. taps 9/10/11 equal), the "rated tap" you enter must be 9 — otherwise the displayed tap position is off by 2. Always record the real tap and confirm the tester's displayed tap matches before trusting the error %.
  2. Yd / Dy connection conversion is done wrong. For mixed star-delta windings the line-voltage ratio is not the turns ratio: a Yd connection gives line ratio = turns ratio ÷ √3, and a Dy gives line ratio = turns ratio × √3. If you compare the nameplate (usually a line ratio) to the instrument's turns ratio without the √3 factor, you see a false ~73% or ~173% "error." Always set the correct vector group (or use blind/auto) and compare line-to-line against line-to-line.
  3. Remanence (剩磁) shifts the first reading. Residual DC magnetism left by a previous winding-resistance or DC test biases the first ratio reading, especially on large transformers. Demagnetise the core (or let it settle) and re-measure; if the first reading drifts, take the stable value, not the first one.

One more, non-negotiable: never test a transformer that is energised or not earthed — the ratio tester excites the windings and a live core is dangerous.

Two more we check before energising

Leads mapped the wrong way. Swapping HV/LV, or A/B/C against a/b/c, gives a nonsense ratio or a wrong vector group. Verify the colour-to-phase mapping on both sides before you press start — the manual's wiring diagram is explicit about yellow/green/red to A/B/C.

Comparing unlike quantities. The instrument can report either the turns ratio or the line ratio depending on the connection group you set. Make sure you are comparing the nameplate's ratio basis (line or phase, star or delta) to the same basis on the screen — this is the root cause of most "the ratio is wrong" false alarms on site.

Not sure which ratio tester fits your transformers — bench with battery, AC bench, or hand-held? Send us the voltage class and whether you test CT/PT too; our engineers will size it and quote within 24 hours.

Ask an engineer — reply within 24 h

Need a turns ratio tester sized for your transformers?

Tell us the voltage class, whether you also test CT/PT, and if you need battery or hand-held — we will propose YA2010L, YA2010 or YA8631S and quote within 24 hours.

Send Inquiry